日本+无码+z,黑人巨大精品欧美一区二区,无码国产精成人午夜视频一区二区,在教室伦流澡到高潮h强圩电影

Leave Your Message
*姓名不能為空!
* 留言內(nèi)容不能為空!
Product
Recommended products

Single water pump controller

This series of single water pump controllers are widely used in submersible sewage pumps, deep well water supply pumps, fire pressure stabilizing pumps, multi-stage centrifugal pumps, sewage lifting devices and other equipment. It is suitable for direct starting, float, pressure, etc. of water pumps below 22KW. control.

    Product overview

    ?

    This series of single water pump controllers are widely used in submersible sewage pumps, deep well water supply pumps, fire pressure stabilizing pumps, multi-stage centrifugal pumps, sewage lifting devices and other equipment. It is suitable for direct starting, float, pressure, etc. of water pumps below 22KW. control.

    ?

    Model description

    Single water pump controller.jpg

    Wiring port description

    ?

    Terminal number

    illustrate

    Terminal number

    illustrate

    1

    Working power supply AC220V live wire

    7

    High water level alarm

    2

    Working power supply AC220V neutral line

    8

    Overload protection point

    3

    Contactor coil control point

    9

    /

    4

    /

    10/11

    Fire module DC24V

    5

    Public terminal (passive)

    12/13

    Passive/manual disconnection and automatic closing

    6

    automatic feedback

    ?

    ?

    ?

    Automatic signal wiring description

    ?

    Drainage control: Float connected to 5#, 6# (connected to normally open)

    Water supply control: Float connected to 5#, 6# (connected to normally closed)

    Electric contact pressure gauge: 5# is connected to the moving end, 6# is connected to the lower limit, and 7# is connected to the upper limit.

    Fire linkage: 10# and 11# ports are connected to DC24V, regardless of positive or negative, it will start when power is received and stop when power is lost.

    ?

    Function selection instructions

    ?

    Press and hold the auto button for 5 seconds in the automatic state to switch between float control and pressure control modes. The red light is on for pressure control mode. The factory default red light is off for float control.

    In the manual state, press and hold the manual button for more than 5 seconds to switch the fault signal type of terminal 8 into normally open type and normally closed type. The factory default is normally open type.

    To turn on or off the automatic inspection function, press and hold the start button for 5 seconds in the automatic state to turn on or off the inspection function. When the inspection function is turned on, the inspection indicator light will flash and light up, and the controller will start inspection according to a cycle every 15 days, each start time is 10 seconds.

    Inspection function test method: After turning on the inspection function, press and hold the second pump start button for more than 5 seconds in the automatic state to enter the automatic inspection function.

    ?

    Wiring schematic diagram

    ?

    Single water pump controller.jpg

    ?

    Dimensional drawing

    ?

    Single water pump controller 1.jpg

    ?